RFD-2FTN Flame Detector

RFD-2FTN Flame Detector

a kind of UV-IR flame detector

Aluminum alloy material

Adjustable sensitivity and delay time

The RFD-2FTN flame detector is an UV-IR flame detector. It is able to quickly detect any fire within a wide field of view of 100° and an effective performan

Description

The RFD-2FTN flame detector is an UV-IR flame detector. It is able to quickly detect any fire within a wide field of view of 100° and an effective performance range of 30m. It is provided with the self-diagnostic testing function and waterproof & explosion-proof structure, and can be safely used on the industrial sites such as oil refineries and fuel gas facilities. Its output includes relays, 4-20mA output and RS-485 communication mode.

Product Characteristics

RFD-2FTN is a kind of UV-IR flame detector

It is able to quickly detect any fire within a wide field of view of 100° and an effective performance range of 30m.

It is provided with the self-diagnostic testing function and waterproof & explosion-proof structure, and can be safely used on the industrial sites such as oil refineries and fuel gas facilities.

Its output includes relays, 4-20mA output and RS-485 communication mode.

Be able to suppress false alarms in a good manner, being a kind of, explosion-proof & dustproof product.

Aluminum alloy material

Adjustable sensitivity and delay time

Technical Parameters

Type Ultraviolet and infrared (UV/IR Type ), explosion-proof type
Operating voltage DC 24V, (17~32V, pulsating current can be used) DC 24V, (17~32V, pulsating current can be used)
Formal monitoring distance 30M
Detection angle 90°, conical
Waterproof class IP66/67(KGS)
Electricity consumption Min. 2.0W; Max. 3.6W
Relative humidity 0~95%
Operating temperature -40℃~+75℃
Storage temperature -50~+90℃
Shell Aluminum 6061
Weight About 0.53kg
Appearance 64mm x 75mm , quadrangular, connector 1/2 "NPT
Performance certification FM3260 , GB 15631-2008(CCC)
Output signal •Relay    
 Fire: 1A (250VAC, 30VDC ), A contact;
 Error: 1A (250VAC, 30VDC ), A-B contact
 •4~20mA
 ·RS-485
Explosion-proof grade Ex d IIB+H2 T5 IP66/67(KGS),
Class I Division 1 Groups B,C and D(FMUS)
Class II/III Division 1 Groups E,F and G(FMUS)
T6: -40°F(-40°C) to +176°F(+75°C)(FMUS)
IP66/67 / NEMA 4X(FMUS)
II 2G Ex db IIB+H2 T5 Ta= -40°C to 75°C
IP66 / IP67(ATEX)
Ex db IIB+H2 T5 -40°C to 75°C IP66 / IP67(IECEx)
Ex dIIC T5 Gb DIP A21 TA, T5 IP67(NEPSI)