IFD20 Dual IR-UV Flame Detector

IFD20 Dual IR-UV Flame Detector

Sensor: UV flame sensor, infrared flame sensor

Response spectral range: 185nm~260nm, 4.3μm, 5.0μm

Sampling mode: Real-time optical path sampling

Display mode: LED indication

The IFD20 dual IR-UV flame detector is a kind of new-type intelligent fire detection equipment. This detector is manufactured with the high-performance dual inf

Description

The IFD20 dual IR-UV flame detector is a kind of new-type intelligent fire detection equipment. This detector is manufactured with the high-performance dual infrared sensing technology and the ultraviolet detection technology, as well as the infrared sensor equipment with different wavelengths and narrow-band filtering and the ultraviolet flame sensing equipment of the solar blind band. Among these three sensors, the infrared sensor and the UV sensor are used to reflect the central wavelength of the flame information in different bands, and the other infrared sensor is used to monitor other infrared radiation in the environment. Combined with the flicker characteristics of the flame, the radiation spectrum with flame characteristics can be identified as a fire alarm by means of the operational analysis with the high-speed microprocessor and technical algorithm. The UV flame sensing equipment is able to suppress the interference from the sunlight in a good manner, so as to achieve a fast response to and accurate identification of the flame signal. In addition, this detector can be used for either dual infrared detection or single ultraviolet detection, and can be also used for both infrared and ultraviolet detection at the same time.

Product Characteristics

High measurement accuracy, stable performance, long service life

4~20mA standard analog signal output

Fault and alarm relay node output

LED display, sensitivity indication, and alarm indication

Simple mounting bracket, with easy installation

Low rate of false alarm, for it is based on the actual flame combustion model

Be provided with special optical lens to realize the reliable optical path transmission

The magnetic rod is used to adjust the sensitivity, without requiring the removal of the cap.

Technical Parameters

Sensor UV flame sensor, infrared flame sensor
Response spectral range 185nm~260nm, 4.3μm, 5.0μm
Sampling mode Real-time optical path sampling
Display mode LED indication
Status indication The blinking green lamp indicates the normal operation, and the permanently-illuminated red lamp indicates a fire alarm.
Response time Level l :6-8 seconds
 Level II:18-22 seconds
 Level III :22-26 seconds
 Level IV :3-4 seconds
Output signal 4-20mA current;
 Faulty relay passive output (AC:3A 250V, DC:3A 30V)
 Fire alarm relay passive output (AC:3A 250V, DC:3A 30V)
Operating voltage DC18-30V
Operating current ≤30mA(DC24V)
Installation mode Wall-mounted or suspended
Maximum detection distance 50m 0.3mx0.3m n-heptane flame
Operating temperature -40~+70°C
Operating humidity ≤95%RH(without condensation)
Detection angle IR: 90° UV: 120 °
Shell Aluminum alloy
Weight 0.6Kg±0.05Kg
Electric interface M20X1.5
Explosion-proof mark Ex db IIC T6 Gb/Ex tb IlIC T80°C Db
Degree of protection IP66

Info Request

For all inquiries, please fill in the form below(* are required) to send us a brief message, and we will get back to you as soon as possible.

Home Products Applications Contact