Sensor: Infrared flame sensor
Response spectral range: 4.3um, 5.0um
Sampling mode: Real-time optical path sampling
Display mode: LED indication
Installation mode: Wall-mounted or suspended
IFD20-IR2 dual infrared flame detector is a kind of new-type intelligent fire detection equipment. This detector adopts the high-performance dual infrared sensi
IFD20-IR2 dual infrared flame detector is a kind of new-type intelligent fire detection equipment. This detector adopts the high-performance dual infrared sensing technology, and is provided with three infrared sensors with different wavelengths and narrow-band filtering. One sensor is used to reflect the central wavelength of the flame information, and the other is used to monitor other infrared radiation in the environment. Combined with the flicker characteristics of the flame, the radiation spectrum with flame characteristics can be identified as a fire alarm by means of the operational analysis with the high-speed microprocessor and technical algorithm. This detector is able to suppress the interferences such as sunlight, lightning, electric welding, thermal radiation, electromagnetic interference, mechanical vibration, etc., is provided with strong anti-interference capacity, and can quickly respond to and accurately identify the flame signal.
High measurement accuracy, stable performance, long service life
4~20mA standard analog signal output
Fault and alarm relay node output
LED display, sensitivity indication, and alarm indication
Simple mounting bracket, with easy installation
Low rate of false alarm, for it is based on the actual flame combustion model
Be provided with special optical lens to realize the reliable optical path transmission
The magnetic rod is used to adjust the sensitivity, without requiring the removal of the cap.
Sensor | Infrared flame sensor |
Response spectral range | 4.3um, 5.0um |
Sampling mode | Real-time optical path sampling |
Display mode | LED indication |
Status indication | The blinking green lamp indicates the normal operation, and the permanently-illuminated red lamp indicates a fire alarm. |
Response time | Level l :6-8 seconds Level II:18-22 seconds Level III :22-26 seconds Level IV :3-4 seconds |
Output signal | 4-20mA current; Faulty relay passive output (AC:3A 250V, DC:3A 30V) Fire alarm relay passive output (AC:3A 250V, DC:3A 30V) |
Operating voltage | DC18-30V |
Operating current | ≤30mA(DC24V) |
Installation mode | Wall-mounted or suspended |
Maximum detection distance | 50m 0.3mx0.3m n-heptane flame |
Operating temperature | -40~+70°C |
Operating humidity | ≤95%RH(without condensation) |
Detection angle | 90 ° |
Shell | Aluminum alloy |
Weight | 0.6Kg±0.05Kg |
Electric interface | M20X1.5 |
Explosion-proof mark | Ex db IIC T6 Gb/Ex tb IlIC T80°C Db |
Degree of protection | IP66 |
For all inquiries, please fill in the form below(* are required) to send us a brief message, and we will get back to you as soon as possible.