Main power supply: 220V AC (+ 10%, -15%) 50HZ
Backup power supply: 2 x 12VDC 10Ah lead-acid battery
Power consumption: Overall power consumption< 50 W
Communication interface: Modbus (RS-485), Canbus
The JB-QB-IFP100 fire alarm controller (linkage type) (hereinafter referred to as “IFP100”) is a new-generation two-bus intelligent fire alarm contr
The JB-QB-IFP100 fire alarm controller (linkage type) (hereinafter referred to as “IFP100”) is a new-generation two-bus intelligent fire alarm controller developed and manufactured by this company in accordance with the national standard GB4717-2005 Fire Alarm Control Units and the national standard GB16806-2006 Automatic Control system for Fire Protection. The maximum capacity of the controller is 800-point bus device, 8-point direct control panel and 40-point bus manual control panel.
The IFP100 controller can be equipped or connected with the fire controller graphic display device via a dedicated RS485 interface, and the management department other than the central controller is able to monitor all the alarms displayed on the controller through the graphic display device located in the fire control room . The universal CAN bus interface and the standard MODBUS protocol can provide flexible interconnection with other devices.
IFP100 is provided with a 7-inch TFT LCD with the resolution of 800×480, all-Chinese display, and it can display the equipment type, location, time, date, address number and other information of the specific alarm in detail, so as to enable the operator to accurately, timely and fully grasp the intuitive and definite alarm information.
The linkage relationship can be set for both the 8-point direct control panel and the 40-point bus manual control panel of the system. The linkage relationship is simple and intuitive, and can meet all kinds of complicated linkage settings and linkage control. The user may correct the logic relationship of the controller anytime and anywhere. When there is any error in the logic input, the controller can give a prompt automatically, which is very convenient.
Support 800-point bus device, 8-point direct control device and 40-point bus manual control panel.
Support Modbus(RS485), Canbus in terms of the communication.
AC220V power supply, overall power consumption <50W.
Wall-mounted.
Name of function | Parameter |
Main power supply | 220V AC (+ 10%, -15%) 50HZ |
Backup power supply | 2 x 12VDC 10Ah lead-acid battery |
Power consumption | Overall power consumption< 50 W |
System capacity | 4 loops where each loop can accommodate up to 200 points of bus equipment, 8-point direct control equipment, 40-point bus manual control panel |
Information display | 7-inch TFT LCD (fire alarm information, supervision information, fault information, linkage information, masking information) |
Historical record | Built-in memory, able to record fire alarm, supervision, fault, linkage and operation events, 10000 each; If the number of events recorded exceeds 10000, those newly added events will overflow; therefore, please back up important events in time. |
Printer | It can print the fire alarm information, supervision information, fault information, linkage information and operation information |
Main relay output | Fire alarm relay, fault relay, resettable relay |
Communication interface | Modbus (RS-485), Canbus |
capacity of relay contact | 3A@125VAC/30VDC |
Sound | Speaker, four kinds of sounds (fire alarm, linkage, supervision, fault), 70dB-100dB |
Installation mode | Wall-mounted |
Operating temperature | 0~45℃ |
Operating humidity | <95%RH, no dewing |
For all inquiries, please fill in the form below(* are required) to send us a brief message, and we will get back to you as soon as possible.