FD10 Dual IR-UV Flame Detector

FD10 Dual IR-UV Flame Detector

Corresponding spectral range: 4.3μm, 5.0μm, 185nm~260nm

Detection object: Flame

Sampling mode: Real-time optical path sampling

Display mode: LED display

Degree of protection: IP66

The FD10 dual IR-UV flame detector is a kind of new-type intelligent fire detection equipment. This detector is manufactured with the high-performance dual infr

Description

The FD10 dual IR-UV flame detector is a kind of new-type intelligent fire detection equipment. This detector is manufactured with the high-performance dual infrared sensing technology and the ultraviolet detection technology, as well as the infrared sensor equipment with different wavelengths and narrow-band filtering and the ultraviolet flame sensing equipment of the solar blind band. Among these three sensors, the infrared sensor and the UV sensor are used to reflect the central wavelength of the flame information in different bands, and the other infrared sensor is used to monitor other infrared radiation in the environment. Combined with the flicker characteristics of the flame, the radiation spectrum with flame characteristics can be identified as a fire alarm by means of the operational analysis with the high-speed microprocessor and technical algorithm. The UV flame sensing equipment is able to suppress the interference from the sunlight in a good manner, so as to achieve a fast response to and accurate identification of the flame signal. In addition, this detector can be used for either dual infrared detection or single ultraviolet detection, and can be also used for both infrared and ultraviolet detection at the same time.

Product Characteristics

Be provided with high-speed, low-power, high-performance 32-bit high-precision data processing chip.

Have excellent resistance to radio frequency and electromagnetic interference and strong anti-interference performance.

Have perfect technical algorithms, high-speed response, high stability and strong ability in preventing false alarm.

Detection angle: IR 90°, UV 120°

Have the maximum detection distance of up to 50m.

Have multiple-level sensitivity settings to meet the needs of different occasions.

The magnetic rod is used to adjust the sensitivity, without requiring the removal of the cap.

The explosion-proof design is applicable for dangerous areas on many types of industrial sites

Technical Parameters

Corresponding spectral range 4.3μm, 5.0μm, 185nm~260nm
Detection object Flame
Sampling mode Real-time optical path sampling
Display mode LED display
Status indication The blinking green LED indicates the normal operation (the number blinking times every 3s represents the sensitivity level), and the blinking red LED indicates an alarm.
Operation mode The magnetic rod is used to adjust the sensitivity (4 levels)
Output signal 4~20mA current; one fault relay contact, one alarm relay contact
Response time ≤10s
Explosion-proof mark E xd II C T6 Gb/   Ex tD A21
Degree of protection IP66
Operating voltage DC24V ± 6V
Operating current ≤30mA(DC24V)
Signal output Relay passive contact, 4~20mA output
Maximum detection distance 50m 0.3m*0.3m n-heptane flame
Detection angle IR 90°, UV 120°
Weight 1.5 ± 0.2 kg
Installation mode Wall-mounted or suspended or pipe-clamped
Interface of cable entry device Shell, two NPT1/2 interfaces
Shell copper-free cast aluminum, epoxy resin baking paint finish
Ambient temperature -20℃~+60℃
Relative humidity ≤95%RH(without condensation)