GP6000 Gas Alarm Controller

GP6000 Gas Alarm Controller

Precision: 1%FS

Response time: 1s

Alarm mode: Audible and visible alarms

Installation mode: Wall-mounted, vertical cabinet type

This product is an updated new-generation product manufactured with the introduction of PLC technology. It is a modular gas detection control system, and is com

Description

This product is an updated new-generation product manufactured with the introduction of PLC technology. It is a modular gas detection control system, and is composed of a variety of unit modules with different functions, including GP6DU1 two-way 4-20mA channel module complete with a centralized control function, GP6DU2 two-way 4-20mA channel module and GP6CU control module. The simplified design and configuration of the GP6000 system ensures that the design institutes, end users and engineering service providers can achieve the convenient design, configuration and debugging of the system. This system completely complies with the requirements of the national fire protection standards, and has obtained the type approval certificate for the fire protection products.

The GP6000 system supports a variety of detectors, including combustible gas detectors, toxic gas detectors, flame detectors, temperature detectors and some status switches. Either a three-wire 4-20mA instrument or a two-wire 4-20mA instrument can be connected to the system.

The GP6000 gas detection and alarm system can meet the requirements for different communication interfaces with the upper-level DCS system and the third-party SCADA system. To achieve the linking with the external communication, the GP6000 system provides a standard RS-485 serial communication interface that supports the Modbus RTU protocol, and each channel is provided with two levels of alarm output.

Product Characteristics

Each unit can work independently, with OLED Chinese display, and extremely high detection reliability

Modular design, guide-rail-mounted, flexible configuration

Distributable design of modules; the CAN bus is used inside the module

Can be used with a variety of combustible gas/toxic gas/oxygen detectors and flame detectors in any form

Built-in 32-bit computer, with self-checking function; each way is provided with time-stamped storage of historical record a history with time storage

Each channel is individually displayed and controlled, is provided with password protection, and can be networked

Each detection control unit has two levels of concentration alarm relay outputs

The control logic of the output relay can be controlled by software, and the alarm outputs can be grouped

Display in Chinese or English, with audible and visible display; able to display the gas type and concentration

The corresponding point name and gas type can be identified on the controller

Optional measurement units: %LEL, %V/V, ppm, mg/m3

There are general alarm and general fault relay output, and serial communication output

Have power management and charging function; can be connected with the backup battery which can be automatically switched on in the event of AC failure

The communication protocols can be developed for digital communication as desired by the user

Technical Parameters

Name of function Model
Precision 1%FS
Response time 1s
Display mode OLED Chinese and digital concentration display, able to indicate the gas type
Display of location information Each way can display the location information, bit number and gas type
Alarm mode Audible and visible alarms
Installation mode Wall-mounted, vertical cabinet type
Input signal 4-20mA
Output signal 4-20mA current, RS-485 bus, CAN bus
Output relay of each way Each way has 2 relay outputs
Main relay output 8 programmable relay outputs
Power consumption AC220 power supply, less than 600W
Operating temperature -20°C~65°C
Working power supply AC220V, AC
Built-in DC power supply Built-in 24V, 20A DC power supply
Standby power supply Can be connected with lead-acid battery or UPS
Shell material Steel plate plastic spraying